Measurement of Flux Distribution on 100kVA 3Phase Distribution Transformer Assembled with 45 T-Joint and Mitred Lap Corner Joint with Stagger Yoke by using Search Coil

I. Daut, D.M.M. Ahmad, and S. Taib (Malaysia)

Keywords

Flux distribution, transformer core, search coil

Abstract

This paper describes the result of measurement of flux distribution on 100kVA 3phase distribution transformer assembled with 45o T-joint and mitred lap CORNER joint with stagger yoke. The measurement involves the variation of flux. The flux distributions have been measured using no load test by arrays of search coil in M5 (CGO) grades material of transformer core laminations. The localised flux density at the outer 45o T-joint is 90 mT and rises to be 148 mT at the inner 45o T-joint and the localised flux density at the outer corner-joint is 103 mT and rises to be 198 mT at the inner corner-joint when the transformer core energized 1 T 50Hz. A small amount of flux deviation from the rolling direction occurs at the overlap.

Important Links:



Go Back